<p><SPAN name="link2H_4_0045" id="link2H_4_0045"></SPAN></p>
<h2> XII. THE THREE-WIRE SYSTEM </h2>
<p>THIS invention is covered by United States Patent No. 274,290, issued to
Edison on March 20, 1883. The object of the invention was to provide for
increased economy in the quantity of copper employed for the main
conductors in electric light and power installations of considerable
extent at the same time preserving separate and independent control of
each lamp, motor, or other translating device, upon any one of the various
distribution circuits.</p>
<p>Immediately prior to this invention the highest state of the art of
electrical distribution was represented by Edison's feeder system, which
has already been described as a straight parallel or multiple-arc system
wherein economy of copper was obtained by using separate sets of
conductors—minus load—feeding current at standard potential or
electrical pressure into the mains at centres of distribution.</p>
<p>It should be borne in mind that the incandescent lamp which was accepted
at the time as a standard (and has so remained to the present day) was a
lamp of 110 volts or thereabouts. In using the word "standard," therefore,
it is intended that the same shall apply to lamps of about that voltage,
as well as to electrical circuits of the approximate potential to operate
them.</p>
<p>Briefly stated, the principle involved in the three-wire system is to
provide main circuits of double the standard potential, so as to operate
standard lamps, or other translating devices, in multiple series of two to
each series; and for the purpose of securing independent, individual
control of each unit, to divide each main circuit into any desired number
of derived circuits of standard potential (properly balanced) by means of
a central compensating conductor which would be normally neutral, but
designed to carry any minor excess of current that might flow by reason of
any temporary unbalancing of either side of the main circuit.</p>
<p>Reference to the following diagrams will elucidate this principle more
clearly than words alone can do. For the purpose of increased lucidity we
will first show a plain multiple-series system.</p>
<p>In this diagram G<1S> and G<2S> represent two generators, each
producing current at a potential of 110 volts. By connecting them in
series this potential is doubled, thus providing a main circuit (P and N)
of 220 volts. The figures marked L represent eight lamps of 110 volts
each, in multiple series of two, in four derived circuits. The arrows
indicate the flow of current. By this method each pair of lamps takes,
together, only the same quantity or volume of current required by a single
lamp in a simple multiple-arc system; and, as the cross-section of a
conductor depends upon the quantity of current carried, such an
arrangement as the above would allow the use of conductors of only
one-fourth the cross-section that would be otherwise required. From the
standpoint of economy of investment such an arrangement would be highly
desirable, but considered commercially it is impracticable because the
principle of independent control of each unit would be lost, as the
turning out of a lamp in any series would mean the extinguishment of its
companion also. By referring to the diagram it will be seen that each
series of two forms one continuous path between the main conductors, and
if this path be broken at any one point current will immediately cease to
flow in that particular series.</p>
<p>Edison, by his invention of the three-wire system, overcame this
difficulty entirely, and at the same time conserved approximately, the
saving of copper, as will be apparent from the following illustration of
that system, in its simplest form.</p>
<p>The reference figures are similar to those in the preceding diagram, and
all conditions are also alike except that a central compensating, or
balancing, conductor, PN, is here introduced. This is technically termed
the "neutral" wire, and in the discharge of its functions lies the
solution of the problem of economical distribution. Theoretically, a
three-wire installation is evenly balanced by wiring for an equal number
of lamps on both sides. If all these lamps were always lighted, burned,
and extinguished simultaneously the central conductor would, in fact,
remain neutral, as there would be no current passing through it, except
from lamp to lamp. In practice, however, no such perfect conditions can
obtain, hence the necessity of the provision for balancing in order to
maintain the principle of independent control of each unit.</p>
<p>It will be apparent that the arrangement shown in Fig. 2 comprises
practically two circuits combined in one system, in which the central
conductor, PN, in case of emergency, serves in two capacities—namely,
as negative to generator G<1S> or as positive to generator G<2S>,
although normally neutral. There are two sides to the system, the positive
side being represented by the conductors P and PN, and the negative side
by the conductors PN and N. Each side, if considered separately, has a
potential of about 110 volts, yet the potential of the two outside
conductors, P and N, is 220 volts. The lamps are 110 volts.</p>
<p>In practical use the operation of the system is as follows: If all the
lamps were lighted the current would flow along P and through each pair of
lamps to N, and so back to the source of energy. In this case the balance
is preserved and the central wire remains neutral, as no return current
flows through it to the source of energy. But let us suppose that one lamp
on the positive side is extinguished. None of the other lamps is affected
thereby, but the system is immediately thrown out of balance, and on the
positive side there is an excess of current to this extent which flows
along or through the central conductor and returns to the generator, the
central conductor thus becoming the negative of that side of the system
for the time being. If the lamp extinguished had been one of those on the
negative side of the system results of a similar nature would obtain,
except that the central conductor would for the time being become the
positive of that side, and the excess of current would flow through the
negative, N, back to the source of energy. Thus it will be seen that a
three-wire system, considered as a whole, is elastic in that it may
operate as one when in balance and as two when unbalanced, but in either
event giving independent control of each unit.</p>
<p>For simplicity of illustration a limited number of circuits, shown in Fig.
2, has been employed. In practice, however, where great numbers of lamps
are in use (as, for instance, in New York City, where about 7,000,000
lamps are operated from various central stations), there is constantly
occurring more or less change in the balance of many circuits extending
over considerable distances, but of course there is a net result which is
always on one side of the system or the other for the time being, and this
is met by proper adjustment at the appropriate generator in the station.</p>
<p>In order to make the explanation complete, there is presented another
diagram showing a three-wire system unbalanced:</p>
<p>The reference figures are used as before, but in this case the vertical
lines represent branches taken from the main conductors into buildings or
other spaces to be lighted, and the loops between these branch wires
represent lamps in operation. It will be seen from this sketch that there
are ten lamps on the positive side and twelve on the negative side. Hence,
the net result is an excess of current equal to that required by two lamps
flowing through the central or compensating conductor, which is now acting
as positive to generator G<2S> The arrows show the assumed direction of
flow of current throughout the system, and the small figures at the
arrow-heads the volume of that current expressed in the number of lamps
which it supplies.</p>
<p>The commercial value of this invention may be appreciated from the fact
that by the application of its principles there is effected a saving of 62
1/2 per cent. of the amount of copper over that which would be required
for conductors in any previously devised two-wire system carrying the same
load. This arises from the fact that by the doubling of potential the two
outside mains are reduced to one-quarter the cross-section otherwise
necessary. A saving of 75 per cent. would thus be assured, but the
addition of a third, or compensating, conductor of the same cross-section
as one of the outside mains reduces the total saving to 62 1/2 per cent.</p>
<p>The three-wire system is in universal use throughout the world at the
present day.</p>
<div style="break-after:column;"></div><br />